有(you)的管(guan)道(dao)(dao)設計人員因(yin)不清楚靜(jing)電(dian)接(jie)地(di)(di)范圍而引起設計事(shi)故,因(yin)此著重講述。我國管(guan)道(dao)(dao)靜(jing)電(dian)接(jie)地(di)(di)和(he)跨(kua)接(jie)相關標(biao)準(zhun)規(gui)(gui)范有(you)GB12158《防(fang)止靜(jing)電(dian)事(shi)故通用導則》、HG/T 20675《化工(gong)(gong)企(qi)業靜(jing)電(dian)接(jie)地(di)(di)設計規(gui)(gui)程(cheng)》、SH/T 3097《石(shi)油化工(gong)(gong)靜(jing)電(dian)接(jie)地(di)(di)設計規(gui)(gui)范》等,GB 50235《工(gong)(gong)業金屬管(guan)道(dao)(dao)工(gong)(gong)程(cheng)施工(gong)(gong)規(gui)(gui)范》等規(gui)(gui)范也有(you)專門的章(zhang)節對(dui)管(guan)道(dao)(dao)靜(jing)電(dian)接(jie)地(di)(di)實施作出規(gui)(gui)定。ASME、PIP等國外標(biao)準(zhun)規(gui)(gui)范也有(you)具體(ti)規(gui)(gui)定,國內外一(yi)些(xie)大型公司和(he)工(gong)(gong)程(cheng)建設單位(wei),對(dui)管(guan)道(dao)(dao)靜(jing)電(dian)接(jie)地(di)(di)設計有(you)企(qi)業級(ji)的規(gui)(gui)定。
①. 位于(yu)爆(bao)炸和(he)火(huo)災(zai)危(wei)險區內(nei)的(de)管道應進(jin)行靜(jing)電(dian)接地。在(zai)爆(bao)炸和(he)火(huo)災(zai)危(wei)險區內(nei),可(ke)(ke)能(neng)存(cun)在(zai)可(ke)(ke)燃(ran)氣體和(he)可(ke)(ke)燃(ran)粉(fen)塵積(ji)聚(ju),如果產(chan)生電(dian)火(huo)花,可(ke)(ke)能(neng)引起(qi)火(huo)災(zai)或(huo)爆(bao)炸事故(gu)。為了防止在(zai)電(dian)氣設施(shi)使用過程中產(chan)生電(dian)火(huo)花,引燃(ran)或(huo)引爆(bao)可(ke)(ke)燃(ran)氣體或(huo)可(ke)(ke)燃(ran)粉(fen)塵,爆(bao)炸和(he)火(huo)災(zai)危(wei)險區內(nei)的(de)強、弱電(dian)設施(shi)均需(xu)要選用防爆(bao)型。
②. 氧(yang)(yang)(yang)氣管道應(ying)進行靜電接地。氧(yang)(yang)(yang)氣是一種特(te)殊(shu)的介(jie)質,其本身不燃(ran)(ran)燒,卻(que)是強氧(yang)(yang)(yang)化劑,在純氧(yang)(yang)(yang)的環境中,鋼(gang)管會被點燃(ran)(ran)。因此雖然氧(yang)(yang)(yang)氣不屬(shu)于(yu)可燃(ran)(ran)介(jie)質,但純氧(yang)(yang)(yang)管道必須(xu)良好接地。
③. 氣固(gu)管(guan)道應進行靜電接(jie)地。氣固(gu)管(guan)道在運行過程中會產生(sheng)大(da)量(liang)靜電,必須保(bao)證管(guan)道良(liang)好接(jie)地,防(fang)止大(da)量(liang)靜電集聚。
④. 平(ping)行敷(fu)設(she)的(de)管(guan)(guan)(guan)道,凈距(ju)小于100mm時,應每隔20m,設(she)置(zhi)靜電(dian)跨接。近距(ju)離平(ping)行敷(fu)設(she)的(de)管(guan)(guan)(guan)廊,為保(bao)證兩(liang)根管(guan)(guan)(guan)道等電(dian)位,需(xu)要每隔20m設(she)置(zhi)跨接。
⑤. 管道進(jin)出(chu)裝置界區處應(ying)進(jin)行靜電(dian)接地,防止界外(wai)管道和(he)裝置內管道間電(dian)荷的(de)相互轉移。