①. 單(dan)法蘭式(shi)液位(wei)計的儀表連接頭(管(guan)嘴)距罐底(di)距離應大于(yu)300mm,且處于(yu)易(yi)于(yu)維護(hu)的方位(wei)。


②. 雙(shuang)法(fa)蘭遠(yuan)傳(chuan)式差(cha)壓液位計的安裝高(gao)度不(bu)宜高(gao)于容器上的下取壓法(fa)蘭口,并精確計算出零點和負遷移量;對傳(chuan)導毛細管應用角鋼或(huo)鋼管進行固定,環境(jing)溫(wen)度變化(hua)大的場所應采取絕熱保(bao)溫(wen)措施(shi)。


③. 差壓(ya)(ya)(ya)(ya)變送器測液(ye)位(wei)的上下(xia)取(qu)(qu)壓(ya)(ya)(ya)(ya)管(guan)(guan)(guan)口之間距(ju)離(li)(li)應(ying)(ying)(ying)大于所需(xu)測量(liang)(liang)范(fan)圍。采(cai)用差壓(ya)(ya)(ya)(ya)變送器測液(ye)位(wei)的安裝應(ying)(ying)(ying)符合以(yi)下(xia)要求:上下(xia)取(qu)(qu)壓(ya)(ya)(ya)(ya)儀(yi)(yi)表連(lian)接頭(管(guan)(guan)(guan)嘴)之間距(ju)離(li)(li)應(ying)(ying)(ying)大于所需(xu)測量(liang)(liang)范(fan)圍,下(xia)取(qu)(qu)壓(ya)(ya)(ya)(ya)儀(yi)(yi)表連(lian)接頭(管(guan)(guan)(guan)嘴)距(ju)罐底距(ju)離(li)(li)不小(xiao)于加(jia)200mm,且(qie)避開液(ye)體抽出(chu)口,上取(qu)(qu)壓(ya)(ya)(ya)(ya)儀(yi)(yi)表連(lian)接頭(管(guan)(guan)(guan)嘴)應(ying)(ying)(ying)避開氣相噴入口,無法避開時(shi)應(ying)(ying)(ying)采(cai)取(qu)(qu)防沖(chong)措(cuo)施;測量(liang)(liang)易揮發或(huo)易冷凝介質液(ye)位(wei)時(shi),應(ying)(ying)(ying)在(zai)負(fu)(fu)壓(ya)(ya)(ya)(ya)側(氣相)加(jia)隔離(li)(li)罐或(huo)在(zai)正負(fu)(fu)壓(ya)(ya)(ya)(ya)兩側均加(jia)隔離(li)(li)罐,并(bing)精確計算出(chu)零點和負(fu)(fu)遷(qian)移量(liang)(liang);測量(liang)(liang)蒸汽鍋爐(lu)汽包液(ye)位(wei)時(shi),應(ying)(ying)(ying)安裝溫(wen)度(du)自補償式平(ping)衡容器,并(bing)應(ying)(ying)(ying)對導(dao)壓(ya)(ya)(ya)(ya)管(guan)(guan)(guan)進(jin)行(xing)伴熱(re)和隔熱(re)保溫(wen)。


④. 采用插入式反吹法測量液(ye)位時,插入導(dao)壓管的端部(bu)距罐底至(zhi)少200mm,并切削成斜(xie)坡(po)狀。