最近,筆(bi)者評審某設計(ji)時,發現(xian)電(dian)氣專(zhuan)(zhuan)業圖紙僅有(you)(you)(you)文字(zi)說明“靜(jing)電(dian)接地見工(gong)(gong)藝(yi)專(zhuan)(zhuan)業示(shi)意(yi)”。而(er)工(gong)(gong)藝(yi)專(zhuan)(zhuan)業的所有(you)(you)(you)設計(ji)文件,沒(mei)有(you)(you)(you)提到靜(jing)電(dian)接地的信息。工(gong)(gong)藝(yi)工(gong)(gong)程(cheng)(cheng)師給出“無論什(shen)么管線均(jun)接地”。工(gong)(gong)程(cheng)(cheng)項目靜(jing)電(dian)接地設計(ji)沒(mei)有(you)(you)(you)完成,工(gong)(gong)藝(yi)的答復(fu)也(ye)不太(tai)合理。


  按GB 50160必須靜電接地的介(jie)質管道如下(xia)。


   ①. 對(dui)爆炸(zha)、火災危險場所內可能(neng)產生靜(jing)電(dian)危險的設備和管道,均應采取靜(jing)電(dian)接地措施。


   ②. 在聚(ju)烯烴(jing)樹脂(zhi)處(chu)理(li)(li)系(xi)(xi)(xi)統(tong)(tong)(tong)、輸(shu)送(song)系(xi)(xi)(xi)統(tong)(tong)(tong)和(he)料倉區應設置靜電接(jie)(jie)地(di)系(xi)(xi)(xi)統(tong)(tong)(tong),不(bu)得出(chu)現(xian)不(bu)接(jie)(jie)地(di)的(de)孤(gu)立(li)導體。過去(qu)聚(ju)烯烴(jing)樹脂(zhi)處(chu)理(li)(li)、輸(shu)送(song)、摻混儲存(cun)系(xi)(xi)(xi)統(tong)(tong)(tong)由于靜電接(jie)(jie)地(di)系(xi)(xi)(xi)統(tong)(tong)(tong)不(bu)完善,發生過料倉靜電燃爆事故。因(yin)此(ci)在物料處(chu)理(li)(li)系(xi)(xi)(xi)統(tong)(tong)(tong)和(he)料倉內嚴禁出(chu)現(xian)不(bu)接(jie)(jie)地(di)的(de)孤(gu)立(li)導體,如(ru)排風過濾器的(de)緊固(gu)件(jian)、管道或軟(ruan)(ruan)連接(jie)(jie)管的(de)緊固(gu)件(jian)、振動(dong)篩的(de)軟(ruan)(ruan)連接(jie)(jie)、臨(lin)時接(jie)(jie)料的(de)手推車或器具等。料倉內若(ruo)有金屬凸出(chu)物,必(bi)須做防靜電處(chu)理(li)(li)。


   ③. 可燃(ran)氣體、液(ye)化(hua)烴、可燃(ran)液(ye)體、可燃(ran)固體的(de)管道在(zai)下(xia)列部位應設靜(jing)電接地設施(shi):進出(chu)裝置或(huo)設施(shi)處(chu);爆(bao)炸危險場所的(de)邊界;管道泵及泵入(ru)口永久過濾器(qi)、緩沖器(qi)等。


   ④. 可燃(ran)液(ye)體(ti)、液(ye)化烴的(de)(de)裝卸棧臺和碼(ma)頭的(de)(de)管道、設備、建筑(zhu)物、構(gou)(gou)筑(zhu)物的(de)(de)金屬(shu)構(gou)(gou)件和鐵(tie)路鋼軌等(作(zuo)陰極保護者除外),均應做電氣(qi)連(lian)接并接地(di)。


   ⑤. 汽車(che)罐(guan)車(che)、鐵路罐(guan)車(che)和裝(zhuang)卸(xie)棧臺(tai)應設靜電專用接地線。


   ⑥. 每組專設(she)的(de)靜(jing)電(dian)接地(di)體的(de)接地(di)電(dian)阻值(zhi)宜(yi)小(xiao)于100Ω。


   ⑦. 除(chu)第(di)一類防雷(lei)系(xi)統的獨立(li)避雷(lei)針裝置(zhi)的接(jie)地(di)體(ti)(ti)外(wai),其他用(yong)途的接(jie)地(di)體(ti)(ti),均(jun)可用(yong)于靜電接(jie)地(di)。