最近,筆者評審某設(she)計時,發現電(dian)氣專業(ye)(ye)圖紙僅(jin)有文(wen)字說明(ming)“靜電(dian)接地(di)(di)見工(gong)藝專業(ye)(ye)示意(yi)”。而工(gong)藝專業(ye)(ye)的(de)所有設(she)計文(wen)件,沒有提到(dao)靜電(dian)接地(di)(di)的(de)信(xin)息(xi)。工(gong)藝工(gong)程師給出“無(wu)論什么管(guan)線均接地(di)(di)”。工(gong)程項目(mu)靜電(dian)接地(di)(di)設(she)計沒有完成,工(gong)藝的(de)答(da)復也不(bu)太合(he)理。


  按GB 50160必須靜電(dian)接地的介質管道(dao)如(ru)下(xia)。


   ①. 對爆炸、火(huo)災危險(xian)場(chang)所內可能產生靜電(dian)危險(xian)的設備(bei)和管道,均應采取靜電(dian)接(jie)地措施(shi)。


   ②. 在聚(ju)烯烴樹(shu)脂處(chu)(chu)理系(xi)統(tong)(tong)(tong)、輸送(song)系(xi)統(tong)(tong)(tong)和(he)(he)料(liao)(liao)倉(cang)區應設(she)置(zhi)靜(jing)電(dian)(dian)接(jie)(jie)地(di)(di)(di)系(xi)統(tong)(tong)(tong),不得出(chu)現不接(jie)(jie)地(di)(di)(di)的(de)(de)孤(gu)立(li)導(dao)體。過去聚(ju)烯烴樹(shu)脂處(chu)(chu)理、輸送(song)、摻混儲(chu)存系(xi)統(tong)(tong)(tong)由于(yu)靜(jing)電(dian)(dian)接(jie)(jie)地(di)(di)(di)系(xi)統(tong)(tong)(tong)不完善,發(fa)生過料(liao)(liao)倉(cang)靜(jing)電(dian)(dian)燃(ran)爆事故。因此在物料(liao)(liao)處(chu)(chu)理系(xi)統(tong)(tong)(tong)和(he)(he)料(liao)(liao)倉(cang)內嚴禁出(chu)現不接(jie)(jie)地(di)(di)(di)的(de)(de)孤(gu)立(li)導(dao)體,如排風過濾器的(de)(de)緊固件、管道或(huo)軟(ruan)連(lian)接(jie)(jie)管的(de)(de)緊固件、振動篩的(de)(de)軟(ruan)連(lian)接(jie)(jie)、臨時接(jie)(jie)料(liao)(liao)的(de)(de)手推車(che)或(huo)器具等。料(liao)(liao)倉(cang)內若有金屬(shu)凸出(chu)物,必(bi)須(xu)做防(fang)靜(jing)電(dian)(dian)處(chu)(chu)理。


   ③. 可燃氣體(ti)、液化烴、可燃液體(ti)、可燃固體(ti)的管道(dao)在下列部位(wei)應(ying)設(she)靜電接(jie)地設(she)施(shi):進出(chu)裝置或設(she)施(shi)處;爆炸危險場(chang)所的邊界;管道(dao)泵及(ji)泵入口永久過濾器、緩沖器等。


   ④. 可燃液體、液化(hua)烴的裝卸棧臺和碼頭的管道、設備、建(jian)筑(zhu)物(wu)、構筑(zhu)物(wu)的金屬構件(jian)和鐵路鋼軌等(作陰極保護者除外),均(jun)應做電氣連(lian)接并接地。


   ⑤. 汽車罐車、鐵路罐車和裝(zhuang)卸棧(zhan)臺(tai)應設靜電(dian)專用接(jie)地線。


   ⑥. 每組(zu)專設的(de)靜電接地(di)體的(de)接地(di)電阻值宜小(xiao)于(yu)100Ω。


   ⑦. 除第一(yi)類(lei)防雷系統的(de)(de)(de)獨(du)立避雷針裝置的(de)(de)(de)接(jie)地(di)體外,其他用途的(de)(de)(de)接(jie)地(di)體,均(jun)可用于(yu)靜電接(jie)地(di)。