最(zui)近,筆者評審(shen)某設計(ji)(ji)時,發現電氣專(zhuan)業(ye)圖紙僅(jin)有文(wen)字(zi)說明(ming)“靜電接(jie)地見工(gong)藝(yi)專(zhuan)業(ye)示意”。而(er)工(gong)藝(yi)專(zhuan)業(ye)的(de)所(suo)有設計(ji)(ji)文(wen)件,沒有提到靜電接(jie)地的(de)信息。工(gong)藝(yi)工(gong)程師給出“無論什么管線(xian)均(jun)接(jie)地”。工(gong)程項目靜電接(jie)地設計(ji)(ji)沒有完(wan)成,工(gong)藝(yi)的(de)答(da)復也不太(tai)合(he)理。


  按GB 50160必須靜電(dian)接地的介質管道(dao)如(ru)下。


   ①. 對爆炸、火災危險(xian)場所內可能產生靜電危險(xian)的設備(bei)和管道,均應(ying)采取靜電接地措施。


   ②. 在聚(ju)烯(xi)烴(jing)樹脂處(chu)理(li)系統(tong)(tong)(tong)、輸(shu)送系統(tong)(tong)(tong)和料(liao)(liao)倉(cang)區應設置靜(jing)電(dian)接(jie)地(di)(di)系統(tong)(tong)(tong),不(bu)得出(chu)現不(bu)接(jie)地(di)(di)的(de)孤立導體。過(guo)(guo)去聚(ju)烯(xi)烴(jing)樹脂處(chu)理(li)、輸(shu)送、摻混(hun)儲(chu)存(cun)系統(tong)(tong)(tong)由于靜(jing)電(dian)接(jie)地(di)(di)系統(tong)(tong)(tong)不(bu)完(wan)善,發生過(guo)(guo)料(liao)(liao)倉(cang)靜(jing)電(dian)燃爆事故。因此在物(wu)料(liao)(liao)處(chu)理(li)系統(tong)(tong)(tong)和料(liao)(liao)倉(cang)內(nei)嚴禁(jin)出(chu)現不(bu)接(jie)地(di)(di)的(de)孤立導體,如(ru)排風過(guo)(guo)濾器的(de)緊(jin)(jin)固件(jian)、管道或軟(ruan)連接(jie)管的(de)緊(jin)(jin)固件(jian)、振動篩的(de)軟(ruan)連接(jie)、臨時接(jie)料(liao)(liao)的(de)手推車或器具(ju)等。料(liao)(liao)倉(cang)內(nei)若有金屬(shu)凸出(chu)物(wu),必(bi)須做防靜(jing)電(dian)處(chu)理(li)。


   ③. 可燃氣體(ti)(ti)、液化(hua)烴、可燃液體(ti)(ti)、可燃固體(ti)(ti)的管(guan)道(dao)在(zai)下列(lie)部(bu)位應(ying)設靜電接地設施:進出裝置或設施處;爆炸危險場所(suo)的邊界;管(guan)道(dao)泵(beng)及(ji)泵(beng)入口(kou)永久過濾器(qi)、緩沖器(qi)等。


   ④. 可燃液體、液化(hua)烴的裝卸棧臺和(he)(he)碼頭(tou)的管道、設(she)備、建筑物(wu)、構(gou)筑物(wu)的金(jin)屬(shu)構(gou)件和(he)(he)鐵路(lu)鋼軌等(作陰極保護者除外),均應做電氣連接并接地(di)。


   ⑤. 汽(qi)車(che)罐(guan)車(che)、鐵路(lu)罐(guan)車(che)和裝卸棧臺(tai)應(ying)設(she)靜電專用接地線。


   ⑥. 每組專(zhuan)設的(de)(de)靜電接地(di)(di)體的(de)(de)接地(di)(di)電阻(zu)值宜小于100Ω。


   ⑦. 除第(di)一(yi)類(lei)防雷系統的獨(du)立避雷針裝置的接地(di)體(ti)外,其他(ta)用途(tu)的接地(di)體(ti),均可用于(yu)靜電(dian)接地(di)。