一、埋地干(gan)管敷設


  埋地(di)敷(fu)設(she)俗稱“鋪(pu)設(she)”,其標高一(yi)般在-0.300m-0.400m(室內(nei)地(di)面為(wei)±0.000)為(wei)宜。管(guan)道變(bian)(bian)(bian)徑(jing)(jing)時,DN50mm以(yi)內(nei)的變(bian)(bian)(bian)小兩(liang)號(hao)(hao)、DN70mm以(yi)上的變(bian)(bian)(bian)小一(yi)號(hao)(hao)者不得使(shi)用補心變(bian)(bian)(bian)徑(jing)(jing),因為(wei)易折斷;當DN50mm以(yi)內(nei)的變(bian)(bian)(bian)小三號(hao)(hao),DN70mm 以(yi)上變(bian)(bian)(bian)小兩(liang)號(hao)(hao)者可以(yi)使(shi)用補心變(bian)(bian)(bian)徑(jing)(jing),因為(wei)該狀況下,不可能(neng)補心被折斷(另有規定(ding)者,以(yi)規定(ding)為(wei)準(zhun))。


 不(bu)用(yong)補(bu)心變徑(jing)時,應用(yong)異徑(jing)管(guan)(guan)(guan)(guan)箍和鍍鋅管(guan)(guan)(guan)(guan)套制短管(guan)(guan)(guan)(guan),短管(guan)(guan)(guan)(guan)長度以不(bu)用(yong)管(guan)(guan)(guan)(guan)箍便(bian)能(neng)套絲為(wei)準。


  干管安裝工序可以安排在回填土之前進行鋪設,可根據施工條件確定。在于管鋪設的同時,應將干管至首層立管閥門的一段立管(含閥門)安裝到位。但閥門要調直,其方法是在閥門上口臨時裝一節約1m長的短管(絲扣要正,不得歪斜),用它看直,調閥門下邊的絲扣,調直時應將手輪卸下來。


干(gan)管安裝(zhuang)程序如下:


  1. 按(an)施工圖繪(hui)制草(cao)圖,計(ji)算出加(jia)工尺寸(cun);


  2. 按草圖預(yu)制、調直(zhi)、防腐;


  3. 如(ru)(ru)在回填土(tu)之(zhi)前安(an)(an)裝(zhuang),應(ying)根據設計(ji)標(biao)高(gao)于安(an)(an)裝(zhuang)前砌筑240mm×240mm 磚墩。如(ru)(ru)在回填土(tu)之(zhi)后安(an)(an)裝(zhuang),應(ying)先挖溝(gou)槽,溝(gou)槽挖至(zhi)管(guan)底標(biao)高(gao),不得(de)超挖,如(ru)(ru)有超挖時(shi)應(ying)用磚墊平,管(guan)身應(ying)鋪設在基土(tu)上。詳見(jian)圖2-33 給水干管(guan)安(an)(an)裝(zhuang)流(liu)程(cheng)圖。


33.jpg



二、在(zai)地溝內或設(she)(she)備層內敷設(she)(she)


  在地溝和設(she)備(bei)層內安(an)裝給水干管(guan)(guan),除按施(shi)工圖(tu)繪制(zhi)出草圖(tu)并計算出部分尺(chi)寸外,其余尺(chi)寸要實(shi)測實(shi)量。然后按草圖(tu)所標注的(de)尺(chi)寸,用(yong)相應的(de)方法預制(zhi)加工。安(an)裝管(guan)(guan)道之前應裝好吊(diao)卡、支架。


 安裝合(he)格的(de)給水干管應是:


 1. 要(yao)有約(yue)0.003的坡(po)度坡(po)向泄水點;


 2. 管道(dao)的彎曲(qu)度(du)沒有超(chao)過(guo)0.5mm/m;


 3. 被破壞(huai)的鍍鋅(xin)層(ceng)表面(mian)及管(guan)螺紋露出(chu)部分,應做防腐處(chu)理;


 4. 與相鄰管道排列合理;


 5. 管道(dao)強度試驗(yan)符合要求;


 6. 管(guan)道沖(chong)洗不應(ying)利用排泄強(qiang)度試驗的水(shui)(shui)(shui)作為對管(guan)道系統的沖(chong)洗(這(zhe)不屬于沖(chong)洗),應(ying)用臨時水(shui)(shui)(shui)管(guan)(管(guan)子(zi)斷面積不小于被沖(chong)洗管(guan)道斷面積的60%),接至給水(shui)(shui)(shui)干管(guan)人口處,在室內打(da)開約50%的給水(shui)(shui)(shui)配水(shui)(shui)(shui)點全(quan)開放(fang)水(shui)(shui)(shui);


 7. 沒(mei)有使用偽劣產(chan)品。



三、給水(shui)立管安裝


1. 明裝立(li)管安(an)裝


安裝立管(guan)之前,應從最上層用線墜直吊(diao)至首層對準(zhun)已安裝完畢(bi)的立管(guan)閥門中(zhong)心點,如果閥門在設(she)備層,那么吊(diao)線便是立管(guan)中(zhong)心。按吊(diao)線畫出立管(guan)卡子(zi)(zi)中(zhong)心線(十字線),然后打(da)孔栽(zai)卡子(zi)(zi)。待卡子(zi)(zi)凝固后,將預(yu)制的立管(guan)對號(hao)安裝,安裝時(shi),只要(yao)將調(diao)直時(shi)在三通和立管(guan)絲頭(螺紋)處劃刮的痕跡對正(zheng)即可。


2. 暗裝立管安裝


 暗(an)裝(zhuang)在管(guan)井(jing)(jing)內的立(li)管(guan),應在最上部先栽(zai)一個型鋼支(zhi)架(jia),然后以(yi)此為(wei)基準用線墜吊線至底(di)層,按吊線安裝(zhuang)支(zhi)架(jia)。待支(zhi)架(jia)凝(ning)固后,將已預制立(li)管(guan)按編號安裝(zhuang)全部立(li)管(guan),根據具體情況(kuang),在強度試(shi)驗前盡(jin)量將管(guan)井(jing)(jing)內支(zhi)管(guan)做出墻面。


 安裝(zhuang)(zhuang)在(zai)墻槽內的立管(guan)(guan),應在(zai)結(jie)構施工(gong)時預留(liu)管(guan)(guan)槽,不(bu)可人(ren)工(gong)剔(ti)鑿。立管(guan)(guan)是否要做(zuo)防結(jie)露(lu)保溫(wen)由設計確定(ding)。明裝(zhuang)(zhuang)支管(guan)(guan)做(zuo)出凈墻面(mian)后(hou)加裝(zhuang)(zhuang)臨(lin)時堵。如果暗裝(zhuang)(zhuang)支管(guan)(guan),待支管(guan)(guan)做(zuo)完和立管(guan)(guan)同(tong)時進行強(qiang)度試(shi)驗。待強(qiang)度試(shi)驗完畢后(hou)將臨(lin)時堵拆卸下(xia)來,裝(zhuang)(zhuang)上一節臨(lin)時短管(guan)(guan)(一端套(tao)絲約100mm長)。這(zhe)種短管(guan)(guan)俗稱(cheng)“壓墜管(guan)(guan)”。



四、熱水立管安裝


  熱(re)水立(li)(li)管(guan)(guan)(guan)(guan)安(an)裝(zhuang)(zhuang)是(shi)否應(ying)考慮(lv)熱(re)膨脹,應(ying)由(you)設(she)計考慮(lv)確定(ding),但必(bi)須是(shi)當(dang)立(li)(li)管(guan)(guan)(guan)(guan)熱(re)伸脹時,支管(guan)(guan)(guan)(guan)能自由(you)作徑向移動(dong)。熱(re)水的干管(guan)(guan)(guan)(guan)和(he)立(li)(li)管(guan)(guan)(guan)(guan)一(yi)般應(ying)有回水管(guan)(guan)(guan)(guan)。干管(guan)(guan)(guan)(guan)與立(li)(li)管(guan)(guan)(guan)(guan)的連接方(fang)法(fa)(fa)可參考熱(re)水采(cai)暖系統干管(guan)(guan)(guan)(guan)與立(li)(li)管(guan)(guan)(guan)(guan)的連接方(fang)法(fa)(fa)。明裝(zhuang)(zhuang)立(li)(li)管(guan)(guan)(guan)(guan)穿(chuan)過(guo)樓板(ban)應(ying)裝(zhuang)(zhuang)套管(guan)(guan)(guan)(guan)。


  冷熱(re)水(shui)立(li)管(guan)的(de)間(jian)距(ju)要有(you)一定(ding)的(de)距(ju)離,否(fou)(fou)則支管(guan)無法躲繞立(li)管(guan)。其(qi)間(jian)距(ju),一般(ban)立(li)管(guan)管(guan)徑在(zai)DN32mm以內的(de)不應(ying)小于(yu)120mm;DN≥40mm的(de)不應(ying)小于(yu)150mm.安裝(zhuang)在(zai)管(guan)井(jing)內的(de)立(li)管(guan)要做保(bao)溫(wen)處(chu)理。安裝(zhuang)在(zai)墻槽內的(de)立(li)管(guan)亦應(ying)保(bao)溫(wen),否(fou)(fou)則不但損失(shi)熱(re)量(liang)、降(jiang)低水(shui)溫(wen),而且對(dui)建(jian)筑墻面還有(you)一定(ding)的(de)破壞作用(yong),如圖2-34所示。


34.jpg